Challenge Description
Category: Reverse Engineering / Industrial Control
Difficulty: 🔴 Hard
The cartridge simulates a Clearwater tank-farm shift. Pump P-101 fills the break tank, FCV-2 supplies the distribution network, and demand changes throughout the shift. Complete 60 seconds without tripping the plant and submit the operator token.
The attachment is the same 32 KiB waterworks.gb cartridge used by the other Clearwater training-rig challenges. This time the task looks less like reversing and more like playing a tiny process-control game.
The HMI gives us two controls:
Atoggles pump P-101;Btoggles valve FCV-2.
It also gives us a reassuringly wide safe band of 30–70%. Keep the tank in that band for one minute. Easy, right?
My first instinct was to play by eye: switch the pump on when the level falls, shut the valve if it falls too quickly, and correct whatever the next screen update shows. That approach misses almost everything interesting in the ROM.
The displayed level is only the integer part of a process with hidden fractional momentum. Demand changes every few seconds. Closing the valve reduces tank outflow but creates a separate no-supply path. Alarms have dwell time rather than tripping immediately. A control decision that looks safe now can already have enough accumulated state behind it to cross a boundary later.
The reliable solution was to stop treating the HMI as a game and reverse it as a controller.
TL;DR
- A new shift begins at tank level 50, with P-101 off and FCV-2 open
Atoggles the pump;Btoggles the valve;Startaborts- Pump supply is 48 model units per frame
- Demand follows a 16-entry table and advances every 180 frames
- Closing FCV-2 divides outflow by four but arms a no-supply condition under high demand
- Tank high alarm: level
>= 71 - Tank low alarm: level
< 30 - A persistent alarm trips the plant after 180 alarm frames
- The shift completes after 60 groups of 60 frames
- A stable policy is to leave FCV-2 open and toggle P-101 on at 40%, off at 60%
- A tested PyBoy run lasts exactly 3,600 process frames, remains in the range 40–60, and ends at 54%
- The completion token is:
flag{shift_complete_operator001}
Cartridge Triage
The ROM header gives us a pleasantly simple target:
Title WATERWORKS
Size 0x8000 / 32768 bytes
Cartridge ROM ONLY (type 0x00)
Banking none
External RAM none
Header check 0x9A, valid
SHA-256 41f2bcb3c80267cc7de348ce06c7dfb4ebfbd375a163d1e70d707e9c59e4bef4
There is no memory-bank controller. Every ROM address below 0x8000 is also the corresponding file offset, which makes cross-referencing code and data much less painful.
Following the entry point and main loop produced this gameplay map:
| Address | Role |
|---|---|
0x0150 |
Hardware and application initialization |
0x018A |
Main loop |
0x01FB |
Joypad edge scanner |
0x0272 |
Initialize a new shift |
0x02A1 |
Handle operator controls |
0x02F1 |
Compute supply/outflow difference |
0x0318 |
Fetch current demand-table value |
0x0324 |
Apply positive tank delta |
0x0344 |
Apply negative tank delta |
0x0361 |
Advance demand every 180 frames |
0x0379 |
Classify alarms and enforce trip dwell |
0x03E3 |
Advance the 60-second shift clock |
0x0680 |
Shift-complete screen |
0x0778 |
Completion-token decoder |
0x07C4 |
Sixteen-entry demand curve |
0x0A8E |
Encrypted completion token |
The main loop is organized almost like a small PLC scan:
wait for frame boundary
read operator input
update process model
advance demand profile
evaluate alarms/interlocks
advance shift timer
update HMI
repeat
That structure is why reversing the individual state bytes is more useful than trying to infer behavior from the screen alone.
Reconstructing WRAM
The gameplay routines use a contiguous block beginning at C000. Naming those bytes was the turning point:
| Address | Meaning |
|---|---|
C000 |
Currently held joypad mask |
C001 |
Newly pressed joypad edges |
C002 |
State: 0 title, 1 running, 2 complete, 3 tripped, 4 service |
C003 |
Service-sequence progress |
C004 |
UI/frame counter |
C005 |
Integer tank level |
C006 |
Fractional tank accumulator |
C007 |
Pump P-101 state |
C008 |
Valve FCV-2 state |
C009 |
Demand-table index |
C00A |
Demand frame counter, 0..179 |
C00B |
Alarm code: 0 nominal, 1 high, 2 low, 3 no supply |
C00C |
Common alarm dwell counter |
C00D |
Elapsed shift seconds |
C00E |
Subsecond frame counter, 0..59 |
C00F |
No-supply qualification counter |
C010 |
Screen redraw request |
The new-shift routine at 0x0272 clears the process block, then installs the three visible initial conditions:
0272 xor a
0273 ld ($C006),a ; fractional accumulator = 0
0276 ld ($C007),a ; pump = OFF
0279 ld ($C009),a ; demand index = 0
027C ld ($C00A),a ; demand frame counter = 0
027F ld ($C00B),a ; alarm = NOMINAL
0282 ld ($C00C),a ; alarm dwell = 0
0285 ld ($C00D),a ; elapsed seconds = 0
0288 ld ($C00E),a ; subsecond frames = 0
028B ld ($C00F),a ; no-supply counter = 0
028E ld a,$32
0290 ld ($C005),a ; tank level = 50
0293 ld a,$01
0295 ld ($C008),a ; valve = OPEN
0298 ld ($C010),a ; request redraw
029B ld a,$01
029D ld ($C002),a ; state = RUNNING
02A0 ret
This also resolves a small UI ambiguity: 1 means open/on for both actuator bytes. The pump starts at zero; the valve starts at one.
Controls Are Edges, Not Held Levels
The input handler at 0x02A1 reads newly pressed bits from C001, not the held mask in C000:
02A1 ld a,($C001)
02A4 bit 4,a ; A button
02A6 jr z,$02B3
02A8 ld a,($C007)
02AB xor $01
02AD ld ($C007),a ; toggle P-101
02B3 ld a,($C001)
02B6 bit 5,a ; B button
02B8 jr z,$02C5
02BA ld a,($C008)
02BD xor $01
02BF ld ($C008),a ; toggle FCV-2
02C5 ld a,($C001)
02C8 bit 7,a ; Start
02CA jr z,$02D6
02CC xor a
02CD ld ($C002),a ; abort to title
02D0 ld a,$01
02D2 ld ($C010),a
Holding A does not oscillate the pump every frame. One press generates one rising edge and one toggle. This becomes important later when automating the controller with PyBoy.
The Demand Curve Hiding Beside the Code
The demand lookup at 0x0318 is a direct indexed read:
0318 ld a,($C009)
031B ld e,a
031C ld d,$00
031E ld hl,$07C4
0321 add hl,de
0322 ld a,(hl)
0323 ret
At 0x07C4, the ROM stores:
10 12 18 14 1e 24 2c 34 28 1e 16 12 22 32 1a 14
In decimal:
16, 18, 24, 20, 30, 36, 44, 52,
40, 30, 22, 18, 34, 50, 26, 20
The routine at 0x0361 increments C00A once per process frame. At 0xB4 = 180, it resets the counter and advances C009 modulo 16:
if (++demand_frames == 180) {
demand_frames = 0;
demand_index = (demand_index + 1) & 0x0f;
}
At 60 frames per second, demand changes every three seconds. The sixteen entries cover 48 seconds and then wrap for the final 12 seconds of the shift.
The peak is 52, just above the pump’s fixed capacity of 48. That is a good piece of challenge design: the highest instantaneous demand tells us the tank will sometimes fall even with P-101 on, but it does not justify leaving the pump on. Across most of the curve, 48 is far more supply than the network consumes.
Reversing the Mass-Balance Model
The process calculation begins at 0x02F1:
supply = 0
if pump_on:
supply = 48
outflow = demand[demand_index]
if valve_closed:
outflow >>= 2
Then the routine compares supply and outflow and sends the unsigned difference to one of two helpers:
if (supply >= outflow)
add_to_tank(supply - outflow);
else
remove_from_tank(outflow - supply);
The important detail is that the difference does not directly change the integer percentage at C005. It first changes the 8-bit accumulator at C006.
Positive path, simplified from 0x0324:
sum = fraction + delta;
fraction = sum & 0xff;
if (sum > 0xff) {
level++;
if (level > 100) {
level = 100;
fraction = 0xff;
}
}
Negative path, simplified from 0x0344:
borrow = fraction < delta;
fraction = (fraction - delta) & 0xff;
if (borrow) {
if (level > 0)
level--;
else
fraction = 0;
}
A readable model is therefore:
fraction += supply - outflow
while fraction >= 256:
level += 1
fraction -= 256
while fraction < 0:
level -= 1
fraction += 256
This hidden byte is why pixel-watching is weaker than state-aware control. A displayed level of 60 can mean 60 + 0/256 or 60 + 255/256. Those states look identical but cross to 61 at very different times.
Closing FCV-2 shifts outflow right twice, effectively dividing it by four. That looks like an emergency way to preserve the tank. It is, but only if the distribution side is ignored. The next routine does not ignore it.
Alarm Logic and the Delayed Trip
The alarm classifier at 0x0379 clears C00B and then applies the level thresholds:
level >= 0x47 (71) -> alarm 1, LEVEL HIGH
level < 0x1E (30) -> alarm 2, LEVEL LOW
Notice the exact boundaries. The HMI says the safe band is 30–70%. The assembly agrees: 30 and 70 are safe; 29 and 71 are not.
The no-supply path checks FCV-2 separately:
if (!valve_open && raw_demand >= 30) {
if (no_supply_counter < 200)
no_supply_counter++;
if (no_supply_counter >= 180)
alarm = 3;
} else {
no_supply_counter = 0;
}
This means the one-quarter outflow shortcut is not free. During high raw demand, a closed valve first accumulates its own qualification timer. Once alarm 3 is active, the common alarm dwell begins accumulating too.
For any active alarm, C00C increments. At 180 alarm frames the ROM switches to state 3:
C002 = 3 PLANT TRIPPED
C010 = 1 redraw
If conditions return to normal before the trip, the common dwell counter decays one count per frame rather than resetting instantly. That is another small piece of process realism hidden behind the simple display.
My initial “shut the valve if the tank falls” instinct was therefore the wrong control objective. It protects inventory by withholding supply from the simulated network, and the program explicitly monitors that failure mode.
The Shift Clock
The timer at 0x03E3 is independent of the demand timer:
03E3 ld a,($C00E)
03E6 inc a
03E7 ld ($C00E),a
03EA cp $3C ; 60 frames
03EC ret c
03ED xor a
03EE ld ($C00E),a
03F1 ld a,($C00D)
03F4 inc a
03F5 ld ($C00D),a
03F8 cp $3C ; 60 seconds
03FA ret c
03FB ld a,$02
03FD ld ($C002),a ; SHIFT COMPLETE
0400 ld a,$01
0402 ld ($C010),a
0405 ret
The target is exactly 60 groups of 60 process frames: 3,600 frames in running state.
Deriving a Stable Controller
Once the model is written down, the safe strategy is deliberately boring:
- leave FCV-2 open for the entire shift;
- turn P-101 on when level reaches 40%;
- turn P-101 off when level reaches 60%.
This is a two-point hysteresis controller. The 20-point deadband prevents rapid toggling, keeps inventory ten points away from either alarm boundary, and never sacrifices distribution flow.
I first validated it in a small model before touching the emulator:
demand = [
16, 18, 24, 20, 30, 36, 44, 52,
40, 30, 22, 18, 34, 50, 26, 20,
]
level = 50
fraction = 0
pump = False
demand_index = 0
demand_frames = 0
for frame in range(60 * 60):
if level <= 40:
pump = True
elif level >= 60:
pump = False
supply = 48 if pump else 0
outflow = demand[demand_index] # valve remains open
if supply >= outflow:
total = fraction + (supply - outflow)
fraction = total & 0xff
if total > 0xff:
level += 1
else:
delta = outflow - supply
borrow = fraction < delta
fraction = (fraction - delta) & 0xff
if borrow:
level -= 1
demand_frames += 1
if demand_frames == 180:
demand_frames = 0
demand_index = (demand_index + 1) & 0x0f
assert 30 <= level <= 70
print(level)
54
The simulated level remains between exactly 40 and 60. Approximate pump transitions are:
ON 02.42s OFF 05.10s
ON 08.73s OFF 11.68s
ON 14.50s OFF 27.68s
ON 30.53s OFF 33.58s
ON 37.13s OFF 44.80s
ON 49.02s OFF 51.60s
ON 55.60s OFF 58.72s
The long middle ON interval lines up with the sustained high-demand section containing 36, 44, 52, 40 and the later 34, 50 pair.
This is the point where the challenge stopped looking like button timing and started looking like a small, recognizable control problem.
Validating the Policy Against the Real ROM
The model explains the strategy, but I still wanted the unmodified cartridge to execute all 3,600 frames and render the reward itself.
The following script was tested with PyBoy 2.8.1:
from pyboy import PyBoy
STATE = 0xC002
LEVEL = 0xC005
PUMP = 0xC007
VALVE = 0xC008
SECONDS = 0xC00D
gb = PyBoy("waterworks.gb", window="null", sound_emulated=False)
gb.set_emulation_speed(0)
# Finish boot and the first title redraw.
gb.tick(120, render=False, sound=False)
assert gb.memory[STATE] == 0
# button() is a one-frame press followed by an automatic release.
gb.button("start")
gb.tick(2, render=False, sound=False)
assert gb.memory[STATE] == 1
assert gb.memory[LEVEL] == 50
assert gb.memory[PUMP] == 0
assert gb.memory[VALVE] == 1
frames = 0
minimum = 100
maximum = 0
while gb.memory[STATE] == 1:
level = gb.memory[LEVEL]
pump = gb.memory[PUMP]
minimum = min(minimum, level)
maximum = max(maximum, level)
# Keep FCV-2 open. Toggle P-101 at the hysteresis limits.
if (level <= 40 and pump == 0) or (level >= 60 and pump != 0):
gb.button("a")
gb.tick(1, render=False, sound=False)
frames += 1
if frames > 3700:
raise RuntimeError("shift did not terminate")
assert frames == 3600
assert gb.memory[STATE] == 2
assert gb.memory[SECONDS] == 60
assert minimum == 40
assert maximum == 60
assert gb.memory[LEVEL] == 54
# Render the completion screen. Font tile zero is ASCII space.
gb.tick(3, render=False, sound=False)
tiles = (
bytes(gb.memory[0x9922:0x9932])
+ bytes(gb.memory[0x9942:0x9952])
)
token = bytes((tile + 0x20) & 0xff for tile in tiles).decode("ascii")
print(token)
gb.stop(save=False)
flag{shift_complete_operator001}
The final assertions are not decorative. They verify that the real ROM:
- stayed in running state for exactly 3,600 frames;
- reached completion state 2 rather than trip state 3;
- counted exactly 60 seconds;
- never left the 40–60 band;
- ended at level 54;
- rendered the expected token into its own tile map.
PyBoy’s Button API Can Eat the Start Press
The 120-frame warm-up in the script is not arbitrary. During early boot and the first title redraw, the program is not yet executing its normal joypad path. Sending Start too early lets PyBoy press and release it before 0x01FB samples the edge.
There are two correct ways to drive a button:
# Convenience API: pressed on the next tick, automatically released after it.
gb.button("start")
gb.tick(2)
# Persistent API: release it explicitly, but only after a pressed tick.
gb.button_press("start")
gb.tick(1)
gb.button_release("start")
gb.tick(1)
This form is wrong for an edge-triggered ROM:
gb.button("start")
gb.button_release("start")
gb.tick(2)
I tested it. The press and release collapse before the ROM observes the edge, C001 remains clear, and the cartridge stays on the title screen.
The same rule applies to every pump toggle. button("a") already creates the required press/release pair. Adding an immediate manual release makes the controller appear to run while silently dropping commands.
Following the Reward Path
Reaching state 2 dispatches to the shift-complete renderer at 0x0680. The fixed strings say:
SHIFT COMPLETE
TANK HELD IN BAND
FOR THE FULL SHIFT.
SHIFT TOKEN:
The token itself is not stored as plaintext. The renderer points HL at 0x0A8E, initializes C = 0xB7, and calls 0x0778 twice for two 16-character rows.
0778 ld a,(hl+) ; ciphertext byte
0779 xor c ; plaintext ASCII
077A sub $20 ; ASCII -> font tile index
077C ld (de),a
077D inc de
077E ld a,c
077F rlca ; rotate key left by one bit
0780 add a,$13
0782 ld c,a ; next key
0783 dec b
0784 jr nz,$0778
0786 ret
The SUB 0x20 is display conversion, not encryption. Before that subtraction, the plaintext relation is:
plaintext[i] = ciphertext[i] XOR key
key = ROL8(key, 1) + 0x13 mod 256
initial key = 0xB7
Static Token Recovery
The 32 ciphertext bytes at 0x0A8E–0x0AAD can also be decoded directly:
from pathlib import Path
rom = Path("waterworks.gb").read_bytes()
cipher = rom[0x0A8E:0x0AAE]
key = 0xB7
plain = bytearray()
for byte in cipher:
plain.append(byte ^ key)
key = ((((key << 1) | (key >> 7)) & 0xff) + 0x13) & 0xff
print(plain.decode("ascii"))
flag{shift_complete_operator001}
There are therefore two complete solution paths:
- reverse the process and operate the real ROM safely for 60 seconds;
- follow the completion renderer and recover the reward statically.
I prefer doing both. The first validates the control model. The second proves that the token extracted from VRAM is generated by the decoder we identified rather than being a fortunate screen scrape.
Flag
flag{shift_complete_operator001}
Reflection
The nicest part of this challenge is that the rolling-XOR flag decoder is not the hard part. The real challenge is recognizing a credible control loop inside a Game Boy ROM:
- fixed pump capacity;
- time-varying network demand;
- an actuator that trades tank retention for service loss;
- fractional state hidden behind an integer display;
- alarm qualification and persistence rather than instant failure;
- a finite operating horizon.
The first tempting “fix” is to close the valve when inventory falls. The ROM punishes that because a treatment plant is not successful merely because its own tank remains full; it must keep supplying the network. The second tempting fix is to leave the pump on. The demand table punishes that with a high-level trip.
The final solution is exactly what I would want from a small real controller: keep the downstream path available and apply hysteresis around the inventory target.
Reverse engineering told me what the plant was doing. A simple control policy told me what to do back. PyBoy then proved that both interpretations were correct for every frame of the actual cartridge.